• VIPA CPU 313SC DPM 313-6CF23

 313-6CF23 - CPUs | CPUs STEP7 programmable, class C

Order no.

313-6CF23

Type VIPA CPU 313SC DPM

General information

Note -
Features Powered by SPEED7
Work memory [KB]: 256...1.024
Onboard 16x DI / 16x DO / 3x Counter / 3x PWM
Interface [RJ45]: Ethernet PG/OP communication
Interface [2x RS485]: MPI, PROFIBUS master/slave, PtP: ASCII, STX/ETX, 3964 (R), USS master, Modbus master/slave
Including front connector
SD/MMC card slot with locking, up to 32 modules stackable, programmable with WinPLC7, SIMATIC Manager and TIA Portal
SPEED-Bus -

Technical data power supply

Power supply (rated value) DC 24 V
Power supply (permitted range) DC 20.4...28.8 V
Reverse polarity protection  
Current consumption (no-load operation) 200 mA
Current consumption (rated value) 900 mA
Inrush current 11 A
I²t 0.7 A²s
Max. current drain at backplane bus 3 A
Max. current drain load supply -
Power loss 14 W

Technical data digital inputs

Number of inputs 16
Cable length, shielded 1000 m
Cable length, unshielded 600 m
Rated load voltage DC 24 V
Reverse polarity protection of rated load voltage  
Current consumption from load voltage L+ (without load) 70 mA
Rated value DC 24 V
Input voltage for signal "0" DC 0...5 V
Input voltage for signal "1" DC 15...28.8 V
Input voltage hysteresis -
Signal logic input Sinking input
Frequency range -
Input resistance -
Input current for signal "1" 6 mA
Connection of Two-Wire-BEROs possible  
Max. permissible BERO quiescent current 1.5 mA
Input delay of "0" to "1" 0.1 / 0.35 ms
Input delay of "1" to "0" 0.1 / 0.35 ms
Number of simultaneously utilizable inputs horizontal configuration 16
Number of simultaneously utilizable inputs vertical configuration 16
Input characteristic curve IEC 61131-2, type 1
Initial data size 2 Byte

Technical data digital outputs

Number of outputs 16
Cable length, shielded 1000 m
Cable length, unshielded 600 m
Rated load voltage DC 24 V
Reverse polarity protection of rated load voltage -
Current consumption from load voltage L+ (without load) 100 mA
Total current per group, horizontal configuration, 40°C 3 A
Total current per group, horizontal configuration, 60°C 2 A
Total current per group, vertical configuration 2 A
Output voltage signal "1" at min. current L+ (-0.8 V)
Output voltage signal "1" at max. current L+ (-0.8 V)
Output current at signal "1", rated value 0.5 A
Signal logic output Sourcing output
Output current, permitted range to 40°C 5 mA to 0.6 A
Output current, permitted range to 60°C 5 mA to 0.6 A
Output current at signal "0" max. (residual current) 0.5 mA
Output delay of "0" to "1" 100 µs
Output delay of "1" to "0" 100 µs
Minimum load current -
Lamp load 5 W
Parallel switching of outputs for redundant control of a load possible
Parallel switching of outputs for increased power not possible
Actuation of digital input  
Switching frequency with resistive load max. 2.5 kHz
Switching frequency with inductive load max. 0.5 Hz
Switching frequency on lamp load max. 2.5 kHz
Internal limitation of inductive shut-off voltage L+ (-52 V)
Short-circuit protection of output yes, electronic
Trigger level 1 A
Number of operating cycle of relay outputs -
Switching capacity of contacts -
Output data size 2 Byte

Technical data analog inputs

Number of inputs -
Cable length, shielded -
Rated load voltage -
Reverse polarity protection of rated load voltage -
Current consumption from load voltage L+ (without load) -
Voltage inputs -
Min. input resistance (voltage range) -
Input voltage ranges -
Operational limit of voltage ranges -
Operational limit of voltage ranges with SFU -
Basic error limit voltage ranges -
Basic error limit voltage ranges with SFU -
Destruction limit voltage -
Current inputs -
Max. input resistance (current range) -
Input current ranges -
Operational limit of current ranges -
Operational limit of current ranges with SFU -
Basic error limit current ranges -
Radical error limit current ranges with SFU -
Destruction limit current inputs (electrical current) -
Destruction limit current inputs (voltage) -
Resistance inputs -
Resistance ranges -
Operational limit of resistor ranges -
Operational limit of resistor ranges with SFU -
Basic error limit -
Basic error limit with SFU -
Destruction limit resistance inputs -
Resistance thermometer inputs -
Resistance thermometer ranges -
Operational limit of resistance thermometer ranges -
Operational limit of resistance thermometer ranges with SFU -
Basic error limit thermoresistor ranges -
Basic error limit thermoresistor ranges with SFU -
Destruction limit resistance thermometer inputs -
Thermocouple inputs -
Thermocouple ranges -
Operational limit of thermocouple ranges -
Operational limit of thermocouple ranges with SFU -
Basic error limit thermoelement ranges -
Basic error limit thermoelement ranges with SFU -
Destruction limit thermocouple inputs -
Programmable temperature compensation -
External temperature compensation -
Internal temperature compensation -
Technical unit of temperature measurement -
Resolution in bit -
Measurement principle -
Basic conversion time -
Noise suppression for frequency -
Initial data size -

Technical data analog outputs

Number of outputs -
Cable length, shielded -
Rated load voltage -
Reverse polarity protection of rated load voltage -
Current consumption from load voltage L+ (without load) -
Voltage output short-circuit protection -
Voltage outputs -
Min. load resistance (voltage range) -
Max. capacitive load (current range) -
Max. inductive load (current range) -
Output voltage ranges -
Operational limit of voltage ranges -
Basic error limit voltage ranges with SFU -
Destruction limit against external applied voltage -
Current outputs -
Max. in load resistance (current range) -
Max. inductive load (current range) -
Typ. open circuit voltage current output -
Output current ranges -
Operational limit of current ranges -
Radical error limit current ranges with SFU -
Destruction limit against external applied voltage -
Settling time for ohmic load -
Settling time for capacitive load -
Settling time for inductive load -
Resolution in bit -
Conversion time -
Substitute value can be applied -
Output data size -

Technical data counters

Number of counters 3
Counter width 32 Bit
Maximum input frequency 30 kHz
Maximum count frequency 30 kHz
Mode incremental encoder  
Mode pulse / direction  
Mode pulse  
Mode frequency counter  
Mode period measurement  
Gate input available  
Latch input available  
Reset input available -
Counter output available  

Write a review

Note: HTML is not translated!
    Bad           Good

VIPA CPU 313SC DPM 313-6CF23

  • Brand: Yaskawa
  • Product Code: 3136CF23
  • Availability: In Stock
  • $0.00

  • Ex Tax: $0.00